1119312

1119312

1119312

LAPP Cable

VDE-registered oil-resistant PVC control cable for a wide range of applications

ÖLFLEX® CLASSIC 110 - PVC control cable, VDE registered, oil resistant and flexible for various applications, 300/500V, also for YSLY or YY
Contact us for lead time

Click below to request a quote for this item. Or for product advice, stock and lead time enquiries call our team on 0330 313 3220.

More Information
Attribute Value
Product Brand Name ÖLFLEX® CLASSIC 110
Approvals
  • VDE reg. no. 7030 for the following sizes:up to 2.5 mm²: 2 - 65 coresfrom 4 mm²: 2 - 7 coresfrom 25 mm²: 2 - 5 cores
Extended Description Benefits
  • Wide choice of standardized lengths and individual cuts
  • Very broad range, items with up to 100 conductors
Applications
  • For fixed installation as well as occasional flexing at free, non-continuously recurring movement without tensile load
  • Dry or damp rooms that are subject to medium mechanical loads
  • Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG)
  • In power chains for a travelling distance up to 5 m and 0,2 ... 1 million bending cycles, for following dimensions: 0,5 to 2.5mm² and 2 to 7 conductors
Features
  • Flame-retardant according IEC 60332-1-2
  • Good chemical resistance, see catalogue appendix T1
  • Oil-resistant according to DIN EN 50290-2-22 (TM54)
Product make up
  • Fine-wire strand made of bare copper wires
  • PVC insulation LAPP P8/1
  • Cores twisted in layers
  • PVC outer sheath, grey (similar RAL 7001)
Manufacturer Lapp
Chemical resistant Yes
Power Chain Yes
Number of conductors 12
mm2 per conductor 1.5
Protective Conductor Yes
Outer Diameter (mm) 12
Copper index kg per km 173.0000
Benefits
  • Wide choice of standardized lengths and individual cuts
  • Very broad range, items with up to 100 conductors
Technical Data Core identification code
  • Black with white numbers acc. to VDE 0293-334
Conductor stranding
  • Fine wire according to DIN EN 60228 (VDE 0295), class 5 / IEC 60228 class 5
Minimum bending radius
  • Occasional flexing: 10 x outer diameter
  • In power chains: 15 x outer diameter
  • Fixed installation: 4 x outer diameter
Nominal voltage
  • U0/U: 300/500 V
Test voltage
  • 4000 V
Temperature range
  • Occasional flexing: -15°C to +70°C
  • In power chains: -5°C to +70°C
  • Fixed installation: -40°C to +80°C
Weight kg per km 279.0000
More Information
Attribute Value
Data Sheet Click here to view

Related Products

  1. 1123589
  2. 1600198
  3. 1123202
  4. 1136205
  5. 1136855