1123412

1123412

1123412

LAPP Cable

0.6/1kVAC, Halogen-free, Flexible, IEC 60332-3, IEC 61034-2, UV/ ozone resistance, UL AWM 1000V

ÖLFLEX® CLASSIC 130 H BK 0,6/1 kV Power and Control Cable UL AWM Style 21156, Conductor class 5, Halogen-free/ Highly Flame Retardant, Public buildings, Outdoor
Contact us for lead time

Click below to request a quote for this item. Or for product advice, stock and lead time enquiries call our team on 0330 313 3220.

More Information
Attribute Value
Product Brand Name ÖLFLEX® CLASSIC 130 H BK 0,6/1 kV
Approvals
  • Based on EN 50525-3-11
  • UL AWM approval: refer to data sheet
Extended Description Benefits
  • Easy installation due to flexible design
Applications
  • Plant engineering, Industrial machinery, Heating and air-conditioning systems
  • Particularly where human and animal life as well as valuable property are exposed to high risk of fire hazards
  • For outdoor applications
  • According to NFPA 79, subchapter 12.9.2: Use for industrial machinery operated in the USA on the basis of UL AWM (recognized) certification
  • Each dimension with nominal/ minimum average wall thickness of the outer sheath of at least 1.8 mm: For applications where a strengthened outer sheath may turn out to be advantageous
Features
  • Flame-retardant according to IEC 60332-1-2 (flame spread on a single cable)
  • No flame-propagation according to IEC 60332-3-24 respectively IEC 60332-3-25 (Flame spread on vertical cable or wire bundle)
  • Halogen-free according to IEC 60754-1 (amount of halogen acid gas - Corrosiveness of combustion gases according to IEC 60754-2 (degree of acidity)
  • Low smoke density according to IEC 61034-2
  • UV and weather-resistant according to ISO 4892-2
  • Ozone-resistant according to EN 50396
Product make up
  • Fine-wire strand made of bare copper wires
  • Core insulation: Halogen-free
  • Outer sheath made of special halogen-free coumpound, black
Manufacturer Lapp
Outdoor Use Yes
Halogen free Yes
Cold resistant Yes
UV Resistant Yes
Flame Retardant Yes
Number of conductors 4
mm2 per conductor 1
Protective Conductor Yes
Outer Diameter (mm) 9.6
Copper index kg per km 38.4
Benefits
  • Easy installation due to flexible design
Technical Data Core identification code
  • Up to 5 cores: colour-coded according to VDE 0293-308, refer to Appendix T9
  • From 6 cores: black with white numbers
Conductor stranding
  • Fine wire according to VDE 0295, class 5/IEC 60228 class 5
Minimum bending radius
  • Occasional flexing: 15 x outer diameter
  • Fixed installation: 4 x outer diameter
Nominal voltage
  • U0/U: 600/1000 V
  • UL: 1000 V
Test voltage
  • 4000 V
Temperature range
  • Occasional flexing: -25°C to +70°C
  • Fixed installation: -40°C to +80°C
  • UL: -25°C to +75°C
Weight kg per km 144.0000
More Information
Attribute Value
Data Sheet Click here to view

Related Products

  1. 1123003
  2. 1123530
  3. 1123251
  4. 1123429
  5. 1119604