0034070
0034070
LAPP Cable
Screened data transmission cable with PE core insulation and pairs in metalfoil
UNITRONIC® Li2YCY PiMF: Low-frequency low-capacitance screened PVC data cable with DIN 47100 coded PE core Pairs in Metal Foil, RS422/ RS485 interface wiring
Contact us for Lead Time
Click below to request a quote for this item. Or for product advice, stock and lead time enquiries call our team on 0330 313 3220.
0034070 Specifications
- Flame-retardant according IEC 60332-1-2
| Attribute | Value |
|---|---|
| Product Brand Name | UNITRONIC® Li2YCY PiMF |
| Extended Description |
Benefits
|
| Benefits | Data transmission cable with low capacitance, pair screening and overall copper braiding | Particularly suitable for wiring data systems and controls in large industrial plants | Individually screened pairs and the overall braid minimise electrical interference | Decoupling of circuits by means of twisted-pair (TP) design (crosstalk effects) |
| Interference rejecting | Yes |
| Number of conductors | 2X2 |
| mm2 per conductor | 1 |
| Outer Diameter (mm) | 11.7 |
| Copper index kg per km | 82 |
| Core Identification Code | 0.22 mm²-0.5 mm²: according to DIN 47100 | 1.0 mm²: a-core: white, b-core: black |
| Characteristic impedance | approx. 85 Ohm (> 1 MHz) |
| Characteristic impedance |
|
| Test Voltage |
|
| Benefits |
|
| Product Make Up |
|
| Product Make Up | 7-wire or fine-wire (from 1 mm²) strands made of bare copper wires | Core insulation made of polyethylene (PE) | Cores twisted into pairs | Foil wrapping, static screening made of aluminium-laminated plastic film with copper drain wire for each pair | Bare copper screen braiding | Outer sheath made of PVC | Outer sheath colour: grey (similar to pebble grey/ RAL 7032) |
| Test Voltage | Core/core: 2000 V | Core/screen: 1000 V |
| Inductivity | Approx. 0.4 mH/km |
| Core Identification Code HTML |
|
| Conductor Stranding | Stranded conductor, based on VDE 0881, 7-wire |
| Conductor Stranding HTML |
|
| Minimum Bending Radius | Occasional flexing: 20 x outer diameter | Fixed installation: 10 x outer diameter |
| Minimum Bending Radius |
|
| Temperature Range |
|
| Technical Data |
Core identification code
|
| Applications |
|
| Weight kg per km | 126 |
| Temperature Range | Occasional flexing: -5°C to +70°C | Fixed installation: -40°C to +80°C |
| Applications | For enhanced requirements in near-end cross-talk attenuation and high electrical interference in the circuits | Suitable for the transmission with varying in frequency and voltage or sensitive signals | Can be used multifunctional in electronics of computer systems, electronic control equipment, office machines, balances, etc. | For measurement value transmission and serial 2-wire interfaces | Intended for limited flexible use, and for fixed installation in dry or damp interiors |
| Features | Flame-retardant according IEC 60332-1-2 |
| Attribute | Value |
|---|---|
| Data Sheet | Click here to view |