30017788

30017788

30017788

LAPP Cable

Halogen-free installation cable in accordance with DIN VDE 0815

J-H(ST)H...BD - telecommunication installation cable, solid conductor/ stationary use, star quads, static foil, halogen-free/ highly flame retardant, VDE 0815
Contact us for lead time

Click below to request a quote for this item. Or for product advice, stock and lead time enquiries call our team on 0330 313 3220.

More Information
Attribute Value
Product Brand Name J-H(ST)H...BD
Approvals
  • In accordance with DIN VDE 0815type J-H(ST)H...BD
Extended Description Benefits
  • Used to meet enhanced fire protection requirements concerning protection of people and high-value property
  • Does not emit any toxic or corrosive gases in the event of fire and resists the spread of fire
  • Aluminium-laminated plastic foil static screen with tin-plated drain wire minimises the interference of high frequency, electromagnetic fields
  • Decoupling of circuits by means of twisted-pair (TP) design (crosstalk effects)
  • J-H(ST)H...BD Fire Alarm Cable is marked with the phrase "Fire alarm cable” at regular intervals on the sheath. It is therefore used especially for installation in fire alarm systems.
Applications
  • This halogen-free, flame-retardant cable with static shielding is made for stationary use for telephone, data and signal transmission in subscriber stations and private branch exchange construction for telephone systems
  • For fixed installation on and under plaster, in dry and damp rooms
Features
  • Flame retardant acc. to DIN VDE 0472-804/08.83, Test method C
  • Halogen-free according to EN 50267-2-1/-2
Product make up
  • Solid bare copper conductor
  • Core insulation made of special halogen-free compound
  • Cores twisted into star quads, 5 star quads are twisted into a bundle, bundles stranded in layers
  • Foil wrapping
  • static screening made of aluminium-laminated plastic film with copper drain wire
  • Outer sheath made of special halogen-free compound
  • Outer sheath colour: grey (RAL 7001)
Halogen free Yes
Flame Retardant Yes
Interference rejecting Yes
Number of conductors 4X2
mm2 per conductor 0.8
Outer Diameter (mm) 9.2
Copper index kg per km 45.0000
Conductor resistance HTML
  • 0.6 mm: max. 130 ohm/km
  • 0.8 mm: max. 73.2 ohm/km
Technical Data Core identification code
  • according to VDE 0815
Conductor stranding
  • 0.6 mm: 0.28 mm²
  • 0.8 mm: 0.50 mm²
Minimum bending radius
  • Fixed installation: 8 x outer diameter
Test voltage
  • Core/core: 800 V
  • Core/screen: 800 V
Conductor resistance
  • 0.6 mm: max. 130 ohm/km
  • 0.8 mm: max. 73.2 ohm/km
Temperature range
  • Occasional flexing: -5°C to +50°C
  • Fixed installation: -30°C to +70°C
Weight kg per km 135.0000
More Information
Attribute Value
Data Sheet Click here to view

Related Products

  1. 0037125
  2. 1591311
  3. 0033204
  4. 0034702
  5. 0034193