Hioki PQ3198 Power Quality Analyser | APC Technology Group

PQ3198

PQ3198

Hioki

Power Quality Analyser

Investigate Power Characteristics and Analyse the Causes of Problems

Hioki portable power meters and analysers are best in class power measuring instruments for measuring single to three-phase lines with a high degree of precision and accuracy. The new and improved PQ3198 is a power quality analyser for monitoring and recording power supply anomalies, allowing their causes to be quickly investigated, and also for assessing power supply problems such as voltage drops, flicker, harmonics, and other electrical issues. New features include the ability to drive current sensors straight from the PQA and enhanced recording capabilities.

Key Features

  • Verify power problems in accordance with the IEC61000-4-30 Edition 3 Class A standard
  • High accuracy and continuous gapless recording
    (V: ±0.1% of nominal voltage, A: ±0.1% rdg. ±0.1% f.s., W: ±0.2% rdg. ±0.1% f.s.)
  • Broadband voltage range lets you measure even high-order harmonic (supraharmonic) components of up to 80 kHz
  • Maximum 6000 V peak transient voltage up to 700 kHz
  • Measure up to 6000 A AC
  • Two systems of power measurement and efficiency calculation for (ch 1, ch 2, ch 3) and ch 4
  • Make simple measurements of inverters with 40 to 70 Hz fundamental frequency and max. 20 kHz carrier frequency
  • Easily create reports with bundled PQ ONE application software 
  • Optional GPS BOX for synchronizing multiple devices
Contact us for lead time

Click below to request a quote for this item. Or for product advice, stock and lead time enquiries call our team on 0330 313 3220.

More Information
Attribute Value
Power Supply AC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery Pack Z1003 (Continuous use: 180 minutes, Charging time: Max. 5 hr 30 m with AC adapter)
Included Accessories Instruction manual ×1, Measurement guide ×1, Voltage Cord L1000 ×1 set (Red/ Yellow/ Blue/ Gray each 1, Black 4, 3m (9.84ft) length, Alligator clip ×8), Spiral tube x20, Color clip, AC Adapter Z1002 ×1, Strap ×1, USB cable (1 m 3.28 ft length) ×1, Battery pack Z1003 ×1, SD Memory Card 2GB Z4001 ×1, Application software (PQ ONE) ×1
Display 6.5-inch TFT color LCD (640 × 480 dots)
Interfaces SD/SDHC memory card, LAN (HTTP server function / FTP function), USB2.0 (for communication)
Measurement Items

1. Transient voltage : 2 MHz sampling
2. Frequency cycle : Calculated as one cycle, 40 to 70 Hz
3. Voltage (1/2) RMS: one cycle calculation refreshed every half cycle
Current (1/2) RMS: half-cycle calculation
4. Voltage swell, Voltage dips, Voltage interruption
5. Inrush current
6. Voltage waveform comparison
7. Instantaneous flicker value: As per IEC61000-4-15
8. 200 ms frequency: Calculated as 10 or 12 cycles,40 to 70 Hz
9. 10 sec frequency: Calculated as the whole-cycle time during the specified 10 s period, 40 to 70 Hz
10. Voltage waveform peak, Current waveform peak
11. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Reactive energy, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor, and efficiency
12. High-order harmonic* component (voltage/ current): 2 kHz to 80 kHz
*Supraharmonic
13. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0th to 50 th orders
14. Harmonic voltage-current phase angle: 1th to 50 th orders
15. Total harmonic distortion factor (voltage/ current)
16. Inter harmonic (voltage/ current): 0.5 th to 49.5 th order
17. K Factor (multiplication factor)
18. IEC Flicker, Δ V10 Flicker
19. Mains signalling voltage

Dimensions and Weight 300 mm (11.81 in)W × 211 mm (8.31 in)H × 68 mm (2.68 in)D, 2.6 kg (91.7 oz) (including Battery Pack Z1003)
Basic Accuracy

Voltage: ±0.1% of nominal voltage
Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy
Active power: ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy

Measurement Lines Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel for voltage, current, power measurement (AC or DC measurement)
Voltage Ranges

Voltage measurement: 600.00 V rms
Transient measurement 6.0000 kV peak

Current Ranges 500.00 mA to 5.0000 kA AC (depends on current sensor in use)
Power Ranges 300.00 W to 3.0000 MW (determined automatically based on voltage and current range in use)
Record

Repeated ON: 1 year, Maximum recording event: 9999 × 366 days (up to 9999 events per day)
Repeated off: 35 days, maximum recording event: 9999 events

More Information
Attribute Value
Data Sheet Click here to view

Related Products

  1. CM3286-50
  2. PW3365
  3. SF1001
  4. PQ3100
  5. PW3360