PW3360
PW3360
Hioki
Clamp On Power Logger
Portable Power Loggers for Energy Audits and Energy Conservation
HIOKI Clamp On Power Meters are multi-channel power measuring devices utilising clamp sensor input to accurately and safely measure power on single-phase to three-phase lines. The PW3360 compact 3-Phase 4-Wire energy loggers monitor power demand and other power parameters to aid in energy audits and validate energy saving measures.
Key Features
- Supports single to three-phase, 4-wire circuits
- Measure between 90V to 780V
- Simultaneously measure up to three single-phase, 2-wire circuits (in the same power system)
- Slim, compact design that can be placed anywhere
- Store months of data on SD cards
- The QUICK SET function guides you in making the right connections
- Choose PW3360-21 for harmonic measurements up to the 40th order
Click below to request a quote for this item. Or for product advice, stock and lead time enquiries call our team on 0330 313 3220.
Attribute | Value |
---|---|
Power Supply |
AC Adapter Z1006: (100 to 240 V AC, 50/60 Hz), 40 VA (including AC adapter) |
Included Accessories | Voltage cord L9438-53 ×1 set, AC adapter Z1006 ×1, USB cable ×1, Instruction manual ×1, Measurement guide ×1, Color clip ×1 set: red, yellow, blue, white/two each, for color-coding clamp sensors, Spiral tubes for grouping clamp sensor cords ×5, Application Software CD (SF4000 GENNECT One) ×1 |
Interfaces |
SD/SDHC memory card |
Measurement Items | Voltage RMS, current RMS, voltage fundamental wave value, current fundamental wave value, voltage fundamental wave phase angle, current fundamental wave phase angle, frequency (U1), voltage waveform peak (absolute value), current waveform peak (absolute value), active power, reactive power (with lag/lead display), apparent power, power factor (with lag/lead display) or displacement power factor (with lag/lead display), active energy (consumption, regeneration), reactive energy (lag, lead), energy cost display, active power demand quantity (consumption, regeneration), reactive power demand quantity (lag, lead), active power demand value (consumption, regeneration), reactive power demand value (lag, lead), power factor demand, pulse input [PW3360-21 only]: Harmonic voltage level, harmonic current level, harmonic power level, content percentage, phase angle, total harmonic distortion (THD-F or THD-R), up to 40th order |
Functions | Connection check, Quick Set navigation guide, clock, pulse input |
Dimensions and Weight |
180 mm (7.09 in) W × 100 mm (3.94 in) H × 48 mm (1.89 in) D, 550 g (19.4 oz) without PW9002 |
Basic Accuracy |
Voltage : ±0.3% rdg. ±0.1% f.s |
Save Destination | SD memory card, or internal memory at real time |
Measurement Lines | 50/60 Hz, Single phase 2 wires (1/2/3 circuits), Single phase 3 wires (1 circuit), Three phases 3 wires (1 circuit), Three phases 4 wires (1 circuit), Current only: 1 to 3 channels |
Voltage Ranges | 600 V AC (Effective measurement range: 90.00 V to 780.00 V) |
Current Ranges |
500.00 mA to 5.0000 kA AC (depends on current sensor in use), |
Power Ranges | 300.00 W to 9.0000 MW (depends on voltage/current combination and measured line type) |
Display Update Rate | 0.5 sec (except when accessing SD card or internal memory, or during LAN/USB communication) |
Data Save Interval | 1 sec to 30 sec, 1 minute to 60 minutes, 14 selections |
Save Items | Measurement value save: Average only / Average, Max./Min. value, [PW3360-21 only]: Harmonic data save: Average only / average, max./min. value in binary format, Screen copy: BMP form (saved every 5 min. at minimum interval time), Waveform save: Binary waveform data |
Attribute | Value |
---|---|
Data Sheet | Click here to view |