Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross or to an Excel® file. (Wireless Adapter Z3210 is necessary)
Detect minuscule leakage currents with a newly designed sensor. (Core jaw diameter up to φ 40 mm)
Broad measurement range extending from leakage currents to load currents
Complies with the performance standard set forth in IEC/EN 61557-13, an international standard on leak clamp meters
Solve GFCI and RCD problems quickly
Speed up pass/fail judgments with the built-in comparator function
CAT IV 300 V\n\nCAT III 600 V
Basic Specifications
AC Current range
6.000 mA, 60.00 mA, 600.0 mA, 6.000 A, 60.00 A, 200.0 A, 6 ranges, True RMS
Basic accuracy 45 Hz - 400 Hz: ±1.0% rdg ±5 dgt (6.000 mA to 6.000 A), ±1.5% rdg ±5 dgt (60.00 A, 200.0 A)
Basic accuracy 15 Hz - 45 Hz, 400 Hz - 2 kHz: ±2.0% rdg ±5 dgt
Defined accuracy range: 0.060 mA to 200.0 A
AC Voltage range
N/A
Frequency range
15.0 Hz to 2000 Hz
Crest factor
3 (other than 200.0 A range), 1.5 (200.0 A range)
Filter function
Cut off frequency: 180 Hz ±30 Hz at filter ON (-3 dB)
Output function
N/A
Other functions
Max/ Min/ AVG/ PEAK MAX/ PEAK MIN value display, Display value hold and auto hold; Backlight, Auto power save, Buzzer sound, Event count display, Comparator, Simple event recording, Rush current measurement